§75.827 — Guarding of trailing cables
 
(a)
Guarding.
 
(1)
The high-voltage cable must be guarded in the following locations:
 
(i)
From the power center cable coupler for a distance of 10 feet inby the power center;
 
(ii)
From the entrance gland for a distance of 10 feet outby the last strain clamp on the continuous mining machine; and,
 
(iii)
At any location where the cable could be damaged by moving equipment.
 
(2)
Guarding must be constructed using nonconductive flame-resistant material or grounded metal.
 
(b)
Suspended cables and cable crossovers. When equipment must cross any portion of the cable, the cable must be either:
 
(1)
Suspended from the mine roof; or
 
(2)
Protected by a cable crossover having the following specifications:
 
(i)
A minimum length of 33 inches;
 
(ii)
A minimum width of 17 inches;
 
(iii)
A minimum height of 3 inches;
 
(iv)
A minimum cable placement area of two and one half-inches (2½″) high by four and one-quarter inches (4¼″) wide;
 
(v)
Made of nonconductive material;
 
(vi)
Made of material with a distinctive color. The color black must not be used; and
 
(vii)
Made of material that has a minimum compressive strength of 6,400 pounds per square inch (psi).

[75 FR 17549, Apr. 6, 2010]