§75.601-3 — Short circuit protection; dual element fuses; current ratings; maximum values

Dual element fuses having adequate current-interrupting capacity shall meet the requirements for short circuit protection of trailing cables as provided in §75.601, however, the current ratings of such devices shall not exceed the maximum values specified in this section:

Conductor size (AWG or MGM)Single conductor cableTwo conductor cable
AmpacityMax. fuse ratingAmpacityMax. fuse rating
141515
122020
102525
860605050
685906570
41101109090
3130150105110
2150150120125
1170175140150
1/0200200170175
2/0235250195200
3/0275300225225
4/0315350260300
250350350285300
300395400310350
350445450335350
400480500360400
450515600385400
500545600415450