§192.189 — Vaults: Drainage and waterproofing
 
(a)
Each vault must be designed so as to minimize the entrance of water.
 
(b)
A vault containing gas piping may not be connected by means of a drain connection to any other underground structure.
 
(c)
Electrical equipment in vaults must conform to the applicable requirements of Class 1, Group D, of the National Electrical Code, NFPA-70 (incorporated by reference, see §192.7).

[35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192-76, 61 FR 26122, May 24, 1996; Amdt. 192-119, 80 FR 181, Jan. 5, 2015]